Product Name:(SCC) (5-20kw) |
Product Detailed: |
Application scenario
Small and medium-sized computer room
Equipment room, wiring room and UPS room
Communication base station room
Machine room of rail transit station
Laboratory, testing room, constant temperature and humidity storage room
Energy conservation and environmental protection
The design of large air volume and small enthalpy difference is suitable for the environment of the machine room and provides a continuous and stable temperature and humidity environment for the main equipment
Design of refrigeration system with high sensible heat ratio, high energy efficiency ratio and high cooling air ratio
The world-famous brand scroll compressor (Copeland or Panasonic) is adopted to ensure the reliable operation of the whole machine
R410A refrigerant is used for high efficiency and environmental protection
Stable and reliable
24-hour uninterrupted operation throughout the year
Ensure the stable temperature and humidity environment of the machine room, and the temperature deviation is less than + / - 1 ℃, and the humidity deviation is + / - 5%
The condenser is made of high corrosion resistant materials, and the standard configuration meets the outdoor temperature environment of - 15 ℃ - 48 ℃
Equipped with low-temperature components, it can meet the northern winter environment of - 35 ℃
The condenser of outdoor unit can automatically control the condensation pressure according to the change of ambient temperature to ensure the normal and reliable operation of condensation pressure.
Easy to use and maintain
4.3-inch touch screen, more complete functions and more convenient operation
It has the functions of expert self diagnosis, fault early warning and automatic start-up
Equipped with standard RS-485 monitoring interface to remotely monitor and set the operation status of air conditioner
Unit parts can be maintained on the front
The factory is pre charged with environment-friendly refrigerant to save installation time and cost
The original factory provides standard three-year warranty
Complete models and flexible configuration
A variety of air supply modes such as up front air supply and top air supply are selected as standard
The range of refrigerating capacity covers 5.6kw/7.5kw/12.5kw/16.2kw/20kw
model SCC005UC SCC005UP SCC008UC SCC008UP SCC012UC SCC012UP SCC016UC SCC016UP SCC020UC SCC020UP
Standard air supply and return mode D-underfloor air supply
Front air supply on u-hood Upper air supply and lower air return Top out air, lower front return air
Optional air cap, with front air supply
Total refrigerating capacity (kW) five point six seven point six twelve point five sixteen point two twenty
Sensible cooling capacity (kW) five point one six point nine eleven point three fifteen point one eighteen point nine
Sensible heat ratio SHR zero point nine one zero point nine one zero point nine zero zero point nine three zero point nine five
Circulating air volume (m3/h) one thousand and seven hundred one thousand and eight hundred three thousand four thousand and two hundred six thousand and five hundred
cryogen R410A
Electrical specifications
Power form 220V AC 1PH 50 Hz 380V AC 3PH 50 Hz
Rated input power of the whole machine (kW) two point three five three four point six five point two seven
Maximum input power (kW) two point nine six five point nine six three point seven two six point seven two six twelve point one five seven point two nine thirteen point two nine eight point nine three fourteen point nine three
Rated input current of the whole machine (A) eleven thirteen point five nine point three twelve fourteen point six
Maximum input current fla (A) thirteen point five twenty-seven point two sixteen point eight thirty point four twelve point nine twenty-two fourteen point one twenty-seven point seven sixteen point seven thirty point three
Annual energy efficiency ratio AEER three point six three point six three point six five three point six five three point eight
compressor
Number of compressors one
Compressor type Rotor compressor Totally enclosed scroll constant frequency compressor
Fan
Number of fans one two
HOOD SIZE
L*W*H (mm) Standard configuration (hood unit integration) 880*700*500 1140*700*500
condenser
Condenser model CS010 CS016 CS022
Refrigerant gas pipe interface (mm) twelve point seven fifteen point eight eight
Refrigerant liquid pipe interface (mm) nine point five two twelve point seven
Water inlet diameter of humidifier (female thread) (mm) G3/4”
Condensate drainage pipe diameter (mm) Φ twenty-two
Heater / humidifier
Heating type / PTC / PTC / PTC / PTC / PTC
Heating quantity (kW) / three / three / six / six / six
Humidification type / electrode / electrode / electrode / electrode / electrode
Humidification amount (kg/hr) / three / three / three / three / three
Size / weight
Indoor unit size L * w * h (mm) 500*485*1750 600*600*1850 880*700*1950 1140*700*1950
Weight of indoor unit (kg) one hundred and sixty one hundred and eighty-six two hundred and forty three hundred and twenty
Outdoor unit size L * w * h (mm) 714*314*686 903*354*1247 1422*545*1098
Weight of outdoor unit (kg) thirty-two fifty-five ninety-nine
Note:
1. The refrigerating capacity is the test result under the conditions of indoor air inlet dry bulb temperature of 24 ° C, wet bulb temperature of 17 ° C and outdoor air inlet dry bulb temperature of 35 ° C
2. The equivalent longest connecting pipe of scc005 / 08 indoor and outdoor units is 30m, and the equivalent longest connecting pipe of scc012 / 16 / 20 indoor and outdoor units is 50m. If the length exceeds this length, please confirm with the manufacturer that scc16 / 20 hood is optional
3. The extension assembly is installed on the liquid pipe, close to the indoor unit, and installed indoors
4. Outdoor ambient temperature range for normal operation of the unit: - 15-48 ° C
|
|